The top model of Metrel’s installation testers is MI 3105 EurotestXA. Features including “All-in-one” installation safety testing, AUTO SEQUENCE ® testing, integrated characteristics of fuses and RCDs (including B type), PASS / FAIL evaluation of test results, 10-level memory structure and built-in battery charger make the EurotestXA an exemplary instrument. Concentrate on your work instead on the instruction manual of your test instrument.
Additional features include TRMS current measurement, 3-wire / one clamp / two clamps earth resistance and 4-wire specific earth resistance measurements, illumination measurement and fuse / fault locator function.
All the results can be quickly saved and then downloaded via the EuroLink PRO software to the computer for evaluation and professional report generation after testing.
The MI 3105 EurotestXA performs continuity, insulation, RCD, loop, line, voltage, frequency, earth resistance and phase sequence testing required by the EN 61557 standard.
Benefits:
Revolutionary AUTO SEQUENCE testing and certifying safety of low voltage electrical installations.
Based on 15 years of research and field experience. Tested and recommended by specialists.
Fast: up to 5 times quicker testing.
Simple: only one single press of a TEST button guides the operator through whole procedure.
Reliable: it acquires up to 50 test results and parameters on each outlet at once. None of necessary test will be forgotten.
Automatic: it gives automatic evaluation of safety status with Pass/Fail certification of overall test results.
Standardised: it generates standardized test report in less than 1 minute.
Safe: automatically detects possible safety hazards for the operator.
Measuring functions:
Insulation resistance with DC voltage;
Continuity of PE conductors with 200 mA test current with polarity change;
Continuity of PE conductors with 7 mA test current (continuous measurement) without RCD tripping;
Line impedance;
Loop impedance;
Loop impedance with Trip Lock RCD function;
TRMS voltage and frequency;
Phase sequence;
RCD testing (general and selective, type AC, A and B);
Earth resistance (3-wire method, one clamp method, two clamps method);
Specific earth resistance (option);
TRMS leakage and load currents;
Overvoltage protection devices testing;
Illumination (option);
Testing of Insulation Monitoring Devices (IMDs);
First fault leakage current in IT systems;
High resolution loop impedance (mΩ).
Standards applied:
Functionality: EN 61557.
Other reference standards for testing: IEC/EN 60364; EN 61008; EN 61009; EN 60755; BS 7671; AS/NZ 3760; CEI 64.8; HD 384; VDE 413
Electromagnetic compatibility (EMC): EN 61326
Safety (LVD): EN 61010-1; EN 61010-031; EN 61010-02-032.
Power Supply Voltage: 9VDC (6x1.5V battery cells or accus., size AA)
Operation: typical 13h
Overvoltage category: 600V CAT III
Protection classification: double insulation
Pollution degree: 2
Protection degree: IP 40
Display: 320x240 dots matrix display with backlight
RS232: 115200 baud
USB: 256000 baud
Continuity:
R Low Ω (EN 61557-4):
Measuring ranges (Ω): 0.16 Ω - 1999 Ω
Test current: min. ±200mA@2Ω
Open-circuit voltage: 6.5V- 9.0V
Continuity 7mA:
Measuring ranges (Ω): 0.0Ω - 1999Ω
Test current: max. 8.5mA
Open-circuit voltage: 6.5V – 9.0V
Insulation resistance (EN 61557-2):
Measuring ranges (MΩ):
Un=50V/100V/250V, R: 0.25MΩ – 199.9MΩ
Un=500V/1kV, R: 0.15MΩ – 999MΩ
Nominal Voltage: 100V, 250V, 500V, 1kV
Measuring current: min. 1mA@Rn=Un x 1kΩ/V
Short-circuit current: < 3mA
Please feel free to contact for detailed specifications, accessories, software and options.