低電壓指令:指令2014/35/EU(CE合格);class I儀器,污染等級2,安裝類別II,符合標準IEC EN 61010-1。
電磁相容性:指令2014/30/EU(CE合格),符合標準EN 61326-1。
CAN/CSA-C22.2 No. 61010-1。
詳細規格、配件、軟體及選購,歡迎洽詢。
Used in a system with BLU device to increase load capacity
Lightweight – starting from 12,5 kg (28 lbs.)
Powerful – discharge power of up to 35 kW
Voltage measurement range: up to 500 V DC
Discharge current – up to 310 A DC
Measurement resolution – current 1 A, voltage 1 V
Discharge process controlled by BLU device
Connects to battery terminals and parallel to BLU device
Application:
Typical application is supporting a BLU device as an additional load in measuring the capacity of the batteries that serve as a backup power supply in (but not limited to):
Power plants
Telecommunication systems
Generator excitation systems
Substations
Protection and control systems
System Overview:
Battery Extra Load Units – BXL Series of devices are designed as an additional load to be used with the BLU series instruments if a required discharge current or power exceeds the capacity of a single BLU device.
The BXL Series of devices are based on the state-of-the-art technology. The devices are based on the most advanced power electronics achievements. Six to eight fans are integrated into the device itself.
The BXL Series are powerful devices providing high discharge currents (up to 310 A DC) applicable to up to 500 V DC battery system voltage levels.
A combination of the BLU and BXL instruments enables performing the capacity test in an accurate, user-friendly way in accordance to battery testing standards (IEEE 450-2010 / 1188-2005 / 1106-2015, IEC 60896-11/22 and other relevant standards).
A BLU device (in a BLU-BXL system) ensures control of the discharge process. BXL simulates constant resistance load during the discharge test – its load parameter (resistance) can be set prior the discharge test.
BXL provides flexibility in selecting its load capacities – several resistances can be set for majority of commercial battery nominal voltage levels.
Three models available:
BXL-A: designed for parallel operation with BLU-A series
BXL-T: designed for parallel operation with BLU220T device
BXL-V: designed for parallel operation with BLU360V device