產品介紹∣Industrial thermometers with male thread
Search

Industrial thermometers with male thread
HVAC version made of aluminium

【SIKA】可攜型乾式高溫校正爐、測試泵、各種流量感測器 溫度測量

Industrial thermometers with male thread

簡介

Type HBZ-WBZ

  • Measuring accuracy according to DIN 16195
  • no ageing, due to no moving parts and no mechanical wear
  • lifetime warranty
  • series production for high-volume users
  • completely without electrical auxiliary energy

我要諮詢

We have modified our industrial thermometer and optimally adapted it to the requirements of heating and air-conditioning applications. In this way we combine an absolutely reliable measuring instrument with an unbeatable price-performance ratio. Two different casing designs and three different casing sizes are available especially for heating and air-conditioning applications.

Casing

Nominal size 110, 150 or 200 mm, aluminium, V-shaped, painted in golden colour. The numbers of the display range are permanently printed on the right-hand side of the scale. Connection of casing and immersion tube by grooved pin and locking screw. Advantage: No turning of the casing required during assembly. The maximum permissible ambient temperature at the housing is 160 °C.

Glass insert (capillary)

Prismatic capillary in rod form made of solid glass, approx. 8 mm Ø, and white background with blue liquid filling. The graduation of the capillary is burnt in black and therefore absolutely durable. Main graduation marks, which correspond to the numbers printed on the casing, are particularly strong and distinctive.

Thermometric filling

In the standard version of up to 200 °C blue thermometric liquid ("Fü").

Immersion tube

Made of brass as a standard, type B with connection thread G½. The diameter of this immersion tube is 10 mm, with a wall thickness of 1 mm. Available in stainless steel on request.

Scale graduation values and error limits

SIKA industrial thermometers meet the requirements of DIN 16195 "Requirements and testing of industrial glass thermometers". Scale graduation values and error limits are defined depending on the casing size and the measuring range. A typical 291 HBZ thermometer for heating applications with a display range of 0...120 °C, for example, has a scale interval of 2 °C and an error limit of 1 °C.

Type 271 HBZ 272 WBZ 291 HBZ 292 WBZ 174 HBZ 175 WBZ
Standard DIN 16181 bis 16190
Version Straight Angle 90° Straight Angle 90° Straight Angle 90°
Dimensions Housing 200 x 36 mm 150 x 36 mm 110 x 36 mm
Measuring range according to DIN Between -30…200 °C
Error limits according to DIN 16195 -30...100 °C = 2 °C
0...120 °C = 2 °C
0...200 °C = 4 °C
-30...120 °C = 2 °C
0...160 °C = 4 °C
2 °C
Medium / Application Liquid and gaseous media
Immersion tube length Between 63...250 mm
Immersion tube diameter Ø 10 mm
Process connection Fixed male thread G½
Pressure rating**
g Immersion tube brass, brazed
g Immersion tube steel or stainless steel, welded
PN 16
PN 35
Medium temperature See selected measurement range
Ambient temperature -20…160 °C
Storage temperature -40…100 °C