MI 2230 VAFMeter is handheld multifunction instrument which can accurately measure voltage, current, power, harmonic distortion and phase angles in single, two and three phase systems.
Measuring Functions:
TRMS Two channel voltage measurements, up to 600 Vac
TRMS Two channel current measurements, up to 3000 Aac
U-U, I-I, U-I angle measurement, phase diagram
Support for three-phase (Aaron) systems
Active, reactive and apparent power, PF, cos φ, THD, frequency
Continuity/resistance of conductors with 200mA test current with polarity change and with pass/fail functionality
Key Features:
Simultaneous measurement and display of voltage, current phase angles and frequency on two or three-phase systems
Accurate phase angle measurement at low current levels
Easy to use: large bright LCD display and large buttons enable easy handling of the instrument
Memory storage for storing up to 1500 measurements
Safe: built for CAT II / 600V environments
Portable: rugged carrying case with a handle and lightweight design enable easy moving the instrument between sites.
Built in charger & rechargeable batteries: instrument has a built-in charging circuit and comes with a set of rechargeable NiMH batteries.
Downloadable: downloads test results via RS232 or USB cable directly to the PC with the help of the Metrel EuroLink software.
Typical Applications:
VAFMeter instrument is designed to be used in general electrical systems maintenance and commissioning, protective relay testing, electrical machine repairs or in monitoring power at the electrical service entrance.
For meter installations, unit measures phase-to-phase voltage and single-phase current amplitudes and phase angles.
Combined with a voltage or current source, instrument also becomes an excellent tool for testing and calibrating virtually any type of protective relay.
Standards:
Functionality:
IEC 61000-4-7
IEC 61557-12
Electromagnetic compatibility:
IEC 61326-1
IEC 61326-2-2
Safety (LVD):
EN 61010-1
EN 61010-031
Voltage Measuring Range and Basic Accuracy: 6 V ... 600 V; ±(0,5 % of reading + 3 digits
Current, Measuring range and Basic Accuracy:
A 1398 - 10 A: 0.1 A ... 20 A; ±(1.5 % of reading + 2 digits)
A 1395 - 30 A: 3 A ... 30 A; ±(1.5 % of reading + 2 digits)
A 1395 - 300 A: 30 A ... 300 A; ±(1.5 % of reading + 2 digits)
A 1395 - 3000 A: 300 A ... 3000 A; ±(1.5 % of reading + 2 digits)
Phase angle:
Measuring range: -180.0 ... +180.0
Basic accuracy: ±0.5°
Please feel free to contact for detailed specifications, accessories, software and options.