體積/重量:寬x高x深(不含把手)205 mm x 287 mm x 410 mm / 10.6 kg。
機身防護等級:IP 43。
安全性標準:
低電壓指令:指令2014/35/EU(CE合格)。
class I儀器適用標準,污染等級2。
安裝類別II:IEC / EN 61010-1。
電磁相容性(EMC):
指令2014/30/EU(CE合格)。
適用標準:EN 61326-1。
詳細規格、配件、軟體及選購,歡迎洽詢。
lightweight – only 10,6 kg / 23.4 lbs
circuit breaker coil operation
spring-charging motor supply
Powerful – up to 40 A
Voltage 10 V to 300 V DC
Voltage 10 V to 250 V AC
Output protection
Fully automatic operation
minimum trip voltage test of the circuit breaker’s coils
as a power supply for tests with breaker analyzers from different vendors
Overview:
Coil Tester & Power Supply POB40D/POB40DL/POB40AD/POB40ADL are powerful, lightweight power supply devices, ideal for operating and testing circuit breakers coils. They are also intended to supply spring-charging motors with the possibility to generate the inrush current of up to 40A DC. For supplying the circuit breaker auxiliary circuits, they provide wide output DC (10 – 300 V) and AC (10 – 250 V) voltage ranges (*depends on the model).
POB40D/POB40DL/POB40AD/POB40ADL have built-in capabilities to perform automatic tests of minimum trip-voltage (in accordance to IEC 62271-100 and ANSI C37.09 standards).
POB40D/POB40DL/POB40AD/POB40ADL can be used as general power supply devices or temporary battery chargers. Note that they are compatible with the circuit breaker analyzers from different vendors.
Application:
The POB series is used in switchyards, power and industrial environment, in manufacturing, in commissioning and as well in maintenance of the circuit breakers for:
operating circuit breakers
supplying spring-charging motors
power supply at test with breaker analyzers
minimum trip voltage-test of the circuit breaker’s coils
The POB series has a built-in capability to perform automatic test of minimum trip voltage. The minimum trip voltage test is described in a number of international and national standards such as IEC 62271-100, ANSI C37.09 etc. Performing tests and acquiring of many other important parameters are possible with circuit breaker analyzers.
The POB series is then used as a power supply unit. It is compatible with breaker analyzers from different vendors. The POB series can also be used as a general power supply unit or temporary battery charger.
Included accessories:
Mains power cable
Ground (PE) cable
Optional accessories:
Transport case
Cable set
External Trigger cable
Mains Power Supply:
Connection according to IEC/EN60320-1; UL498, CSA 22.2
Voltage 90 V – 264 V AC, 50/60 Hz, Single phase
Power consumption 4000 VA
Output data:
Coils output DC Voltage 10 V to 300 V DC (varies for different device models)
Coils output AC Voltage 10 V to 250 V AC (varies for different device models); 50/60 Hz; true RMS
Motor output DC Voltage 10 V to 250 V DC
Output current max 40 A (varies for different device models)
Measurement:
Voltage 10 V – 300 V DC or 10 V – 250 V AC
Current 1 A – 50 A
Accuracy ± (0,25% rdg + 0,25% FS)
Environment conditions:
Operating temperature –10℃- +55℃
Storage and transportation –40℃- +70℃
Humidity: Maximum relative humidity 95%, non-condensing
Dimensions and Weight:
Dimensions (W x H x D) without handle: 205 mm x 287 mm x 410 mm
Weight: 10,60 kg
Mechanical protection: IP 43
Safety Standards:
Low Voltage Directive:
Directive 2014/35/EU (CE conform).
Applicable standards, for a class I instrument, pollution degree 2,
Installation category II: IEC EN 61010-1
Electromagnetic Compatibility (EMC):
Directive 2014/30/EU (CE conform).
Applicable standard: EN 61326-1
Please feel free to contact for detailed specifications, accessories, software and options.